DOI | Trouver le DOI : https://doi.org/10.1109/TIM.2015.2398956 |
---|
Auteur | Rechercher : So, Eddy1; Rechercher : Verhoeven, Rob; Rechercher : Dorpmanns, Luc; Rechercher : Angelo, Dave1 |
---|
Affiliation | - Conseil national de recherches du Canada. Science des mesures et étalons
|
---|
Format | Texte, Article |
---|
Sujet | Electric reactors; Extra high voltage; Measurement uncertainty; Shunt reactors; Three phase; traceability; Uncertainty analysis |
---|
Résumé | An overview of traceability issues of loss measurements of extra high voltage three-phase shunt reactors is presented. Loss measurements of a 345-kV-55-MVAr three-phase shunt reactor at Royal SMIT Transformers, including their uncertainties, are presented and discussed. The measurement results are confirmed with those obtained using a special high-voltage inductance bridge. |
---|
Date de publication | 2015-02-26 |
---|
Dans | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Numéro NPARC | 21275650 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | 7ccb9662-f53d-4371-9236-37c556ede14e |
---|
Enregistrement créé | 2015-07-14 |
---|
Enregistrement modifié | 2020-04-22 |
---|