| DOI | Resolve DOI: https://doi.org/10.1109/TIM.2015.2398956 |
|---|
| Author | Search for: So, Eddy1; Search for: Verhoeven, Rob; Search for: Dorpmanns, Luc; Search for: Angelo, Dave1 |
|---|
| Affiliation | - National Research Council Canada. Measurement Science and Standards
|
|---|
| Format | Text, Article |
|---|
| Subject | Electric reactors; Extra high voltage; Measurement uncertainty; Shunt reactors; Three phase; traceability; Uncertainty analysis |
|---|
| Abstract | An overview of traceability issues of loss measurements of extra high voltage three-phase shunt reactors is presented. Loss measurements of a 345-kV-55-MVAr three-phase shunt reactor at Royal SMIT Transformers, including their uncertainties, are presented and discussed. The measurement results are confirmed with those obtained using a special high-voltage inductance bridge. |
|---|
| Publication date | 2015-02-26 |
|---|
| In | |
|---|
| Language | English |
|---|
| Peer reviewed | Yes |
|---|
| NPARC number | 21275650 |
|---|
| Export citation | Export as RIS |
|---|
| Report a correction | Report a correction (opens in a new tab) |
|---|
| Record identifier | 7ccb9662-f53d-4371-9236-37c556ede14e |
|---|
| Record created | 2015-07-14 |
|---|
| Record modified | 2020-04-22 |
|---|