| Author | Search for: So, Eddy So1; Search for: Verhoeven, Rob; Search for: Simmons, Bart; Search for: Parks, Harold1; Search for: Angelo, Dave1 |
|---|
| Affiliation | - National Research Council Canada. Measurement Science and Standards
|
|---|
| Format | Text, Article |
|---|
| Conference | Conference on Precision Electromagnetic Measurements, July 8-13, 2018, Paris, France |
|---|
| Subject | Extra High Voltage (EHV); multi-ratio; multistage; precision measurements; ratio errors; shunt reactor; three-stage; uncertainty |
|---|
| Abstract | An overvicw of the development and performance of special high prccision multi-ratio three-stage CT and its application for loss measurement of EHV thrcc-phase shunt rcactors with test voltages up to 1050 kV at Royal SMIT Transformcrs arc prcsented and discuss. lt features current ratios of SOOA/I A, 400A/ 1A, 300A/1A, 200A/ IA, and lOOA/lA with ratio crrors of lcss than Sxl0-6 in both magnitude and phase with burdens up to 1.0 Q and at power frcqucncies of 50 Hz - 60 Hz. |
|---|
| Publication date | 2018-07 |
|---|
| Publisher | The Conference |
|---|
| In | |
|---|
| Language | English |
|---|
| Peer reviewed | Yes |
|---|
| NPARC number | 23004102 |
|---|
| Export citation | Export as RIS |
|---|
| Report a correction | Report a correction (opens in a new tab) |
|---|
| Record identifier | 0fcf3fc2-8471-4d7c-93dd-23ef19fd5135 |
|---|
| Record created | 2018-09-27 |
|---|
| Record modified | 2020-03-16 |
|---|